Liquid Column Manometer & Differential Pressure Switch – HK Instruments MM/PS Series

Feature

The filter alerts are a solution for systems requiring visual indication of pressure on site and a switching point signal. The filter alerts are ideal for general-purpose work in air-conditioning and ventilation, especially in monitoring of air filters for contamination.

Enquiry
Category:

Combination of a liquid column manometer and a differential pressure switch

In many situations filter monitoring requires an alarm signal and a local display. Our filter alerts are the right solution for these situations. The filter alerts combine differential pressure switches with manometers into one practical product offering.

The filter alerts are a solution for systems requiring visual indication of pressure on site and a switching point signal. The filter alerts are ideal for general-purpose work in air-conditioning and ventilation, especially in monitoring of air filters for contamination.

Applications

The filter alerts are a solution for systems requiring visual indication of pressure on site and a switching point signal. The filter alerts are ideal for general-purpose work in airconditioning and ventilation, especially in monitoring of air filters for contamination.

Specification

Switching difference: 30 Pa
Accuracy of switching point (low limit typ.): 40 Pa ±5 Pa
Accuracy of switching point (high limit typ.): 600 Pa ±30 Pa
Electrical rating, resistive load: 3 A / 250 VAC
Electrical rating, inductive load: 2 A / 250 VAC
Maximum pressure: 50 kPa
Service life: > 1 000 000 switching operations
Measuring units: Pa
Environment: Operating temperature: -20…+60 °C
Storage temperature: -40…+85 °C
Protection standard: IP54

Download