2-Wire Transmitter With HART Protocol – PR Electronics 5337A

Features

  • RTD, TC, Ohm, and bipolar mV input
  • 2 analog inputs and 5 device variables with status available
  • HART protocol revision selectable from HART 5 or HART 7
  • Hardware assessed for use in SIL applications
  • Mounting in Safe area or Zone 2/22
Enquiry

Application

  • Linearized temperature measurement with TC and RTD sensors e.g. Pt100 and Ni100.
  • HART communication and 4…20 mA analog PV output for individual, difference or average temperature measurement of up to two RTD or TC input sensors.
  • Conversion of linear resistance to a standard analog current signal, e.g from valves or Ohmic level sensors.
  • Amplification of bipolar mV signals to standard 4…20 mA current signals.
  • Up to 63 transmitters (HART 7) can be connected in a multidrop communication setup.

Technical characteristics

  • HART protocol revision can be changed by user configuration to either HART 5 or HART 7 protocol.
  • The HART 7 protocol offers:
    • Long Tag numbers of up to 32 characters.
    • Enhanced Burst Mode and Event notification with time stamping.
    • Device variable and status mapping to any dynamic variable PV, SV, TV or QV.
    • Process signal trend measurement with logs and summary data.
    • Automatic event notification with time stamps.
    • Command aggregation for higher communication efficiency.
  • 5337A is designed according to strict safety requirements and is therefore suitable for applications in SIL installations.
  • Continuous check of vital stored data.
  • Meeting the NAMUR NE21 recommendations, the 5337 HART transmitter ensures top measurement performance in harsh EMC environments. Additionally, the 5337 meets NAMUR NE43 and NE89 recommendations.

Mounting / installation

  • For DIN form B sensor head or DIN rail mounting via the PR fitting type 8421.
  • Configuration via standard HART communication interfaces or by PR 5909 Loop Link.

Specification

ENVIRONMENTAL CONDITIONS
Operating temperature -40°C to +85°C
Calibration temperature 20…28°C
Relative humidity < 95% RH (non-cond.)
Protection degree (encl./terminal) IP68 / IP00
MECHANICAL SPECIFICATIONS
Dimensions Ø 44 x 20.2 mm
Weight approx. 50 g
Wire size 1 x 1.5 mm2 stranded wire
Screw terminal torque 0.4 Nm
Vibration IEC 60068-2-6
2…25 Hz ±1.6 mm
25…100 Hz ±4 g
COMMON SPECIFICATIONS
Supply
Supply voltage 8.0…35 VDC
Isolation voltage
Isolation voltage, test / working 1.5 kVAC / 50 VAC
Response time
Response time (programmable) 1…60 s
Voltage drop 8.0 VDC
Signal / noise ratio > 60 dB
Programming Loop Link & HART
Accuracy Better than 0.05% of selected range
Signal dynamics, input 22 bit
Signal dynamics, output 16 bit
EMC immunity influence < ±0.1% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span
INPUT SPECIFICATIONS
Common input specifications
Max. offset 50% of selected max. value
RTD input
RTD type Pt50/100/200/500/1000; Ni50/100/120/1000
Cable resistance per wire 5 Ω (up to 50 Ω per wire is possible with reduced measurement accuracy)
Sensor current Nom. 0.2 mA
TC input
Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) Constant, internal or external via a Pt100 or Ni100 sensor
Voltage input
Measurement range -800…+800 mV
Min. measurement range (span) 2.5 mV
Input resistance 10 MΩ
OUTPUT SPECIFICATIONS
Current output
Signal range 4…20 mA
Min. signal range 16 mA
Load (@ current output) ≤ (Vsupply – 8) / 0.023 [Ω]
Sensor error indication Programmable 3.5…23 mA
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA
Common output specifications
Updating time 440 ms
HART protocol revisions HART 7 and HART 5
I.S. / EX MARKING
ATEX II 3 G Ex nA [ic] IIC T4…T6 Gc, II 3 G Ex ic IIC T4…T6 Gc, II 3 D Ex ic IIIC Dc
IECEx Ex nA [ic] IIC T4…T6 Gc, Ex ic IIC T4…T6 Gc, Ex ic IIIC Dc
CSA Cl. I, Div. 2, Gp. A, B, C, D T6…T4, Ex nA[ic] IIC T6…T4 Gc
INMETRO Ex nA [ic] IIC T6…T4 Gc, Ex ic IIC T6…T4 Gc, Ex ic IIIC Dc
OBSERVED AUTHORITY REQUIREMENTS
EMC 2014/30/EU
ATEX 2014/34/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011
APPROVALS
DNV-GL Marine TAA0000101
ATEX KEMA 03ATEX1508 X
IECEx KEM 10.0083X
CSA 1125003
INMETRO DEKRA 18.0002X
EAC Ex RU C-DK.HA65.B.00355/19
SIL Hardware assessed for use in SIL applications

Download

PR Electronic 5337A 2-wire transmitter with HART protocol-DpstarGroup