Lutron DW-6092 – 3 Phase Power Analyzer

Features

  • 3 phase/4 wire, 3 phase/3 wire, 1 phase/2 wire, 1 phase/3 wire
  • True rms measurement for ACA, ACV.
  • True power : W, KW, MW.
  • VA, KVA, MVA, VAR, KVAR, MVAR.
  • PF (power factor), phase angle.
  • KWH, KVAH, KVARH, PFH.
  • Voltage measurement range: 10 to 600 ACV
  • Current measurement range: 0.2 A to 1200 ACA.
  • Programmable CT ratio (1 to 600) and PT ratio (1 to 1000).
  • Real time data recorder with SD card.
  • RS232/USB computer interface.
  • Display all measuring electrical wave shape.
  • Patent: Taiwan, China, Japan, Germany, USA pending.
Enquiry

Lutron DW-6092 is a versatile 3-phase power analyzer with capabilities for 3-phase/4-wire, 3-phase/3-wire, 1-phase/2-wire, and 1-phase/3-wire configurations. It offers true RMS measurement for ACA and ACV, along with various power parameters such as true power (W, KW, MW), VA, KVA, MVA, VAR, KVAR, MVAR, PF (power factor), and phase angle. Additionally, it records KWH, KVAH, KVARH, and PFH. With voltage measurement ranging from 10 to 600 ACV and current measurement from 0.2 A to 1200 ACA, it covers a wide range of applications. The device features programmable CT ratio (1 to 600) and PT ratio (1 to 1000), along with a real-time data recorder utilizing an SD card. It also offers RS232/USB computer interface for data transfer and analysis. Furthermore, it displays the electrical wave shape for comprehensive analysis. Pending patents in Taiwan, China, Japan, Germany, and the USA highlight its innovative design.

Specification

Circuit Custom one-chip of microprocessor LSI circuit
Display • LCD Size : 81.4 X 61 mm ( 3.2 X 2.4 inch )
• Dot Matrix LCD (320 X 240 pixels ) with back light
Measurement • ACV
• ACA
• AC WATT ( True Power )
• AC WATT( Apparent Power )
• AC WATT( Reactive Power )
• Power factor
• Phase angle
• Frequency
Wire connections 1P/2W, 1P/3W, 3P/3W, 3P/4W.
Voltage ranges 10 ACV to 600 ACV, auto range.
Current ranges 0.2 ACA to 1200 ACA, auto range/manual range.
Safety standard IEC1010 CAT III 600 V.
ACV input impedance 10 Mega ohms.
Range select ACV : Auto range.
ACA : Auto range & manual range
Clamp  frequency response 40 Hz to 1 KHz.
Spec. tested frequency 45 to 65 Hz
Over load protection ACV  : 720 ACV rms
ACA : 1300 ACA with clamp probe CP-1200
Over Indicator Show ” OL “.
Under Indicator Show ” UR “.
Data Hold Freeze the display reading.
Data Record SD Card Record.
Sampling Time Approx. 1 second.
Power ON/OFF Manual OFF by push button
Real time  data logger • Real time data logger, saved the data into SD memory card and down load the all the measured value with the time information ( year/month/data/ hour/mimute/second ) down load to the Excel

• Integration time for data logger : 2 seconds to 7200 seconds, the during of setting step are 2 seconds.

Data Output USB/RS232
* Computer interface
RS232 computer serial interface :

• Connect the optional USB cable
USB-01 will get the USB plug.

• Connect the optional RS232 cable
UPCB-02 will get the RS232

Operating  Temperature 0 to 50 °C( 0 to 122 °F ).
Operating Humidity Less than 80% R.H..
Power Supply • DC 1.5V, AA ( UM-3 ) Battery X 8 PCs (Alkaline or heavy duty battery).
• AC to DC 9V power adapter.
Power  Consumption • Meter : 300 DCmA
• Clamp : 20 DCmA.
Clamp max. conductor  Size 86 mm ( 3.4 inch ) Dia.
Weight • Meter: 1049g ( includes batteries )
• Clamp : 522g
Dimension • Meter :
225 X 125 X 64 mm
( 8.86 X 4.92 X 2.52 inch )• Clamp :
210 X 64 X 33mm
( 8.3 X 2.5 X 1.3 inch )• Clamp Jaw :
50 mm (2.0 inch)- outside
Accessories Included • Instruction manual………………….. 1 PC
• Test Leads (TL88-4AT)…………. 1 Set (4 PCs)
• Alligator clips (TL88-4AC)……….1 Set (4 PCs)
• Clamp Probe ( CP-1200 )……… 3 PCs
• AC to DC 9V adapter……………..1 PC
• SD card ( 2 G )……………………… 1 PC
• Carrying bag………………………….1 PC
Optional Accessories • USB Cable , USB-01
• RS232 cable, UPCB-02
• Data Acquisition software, SW-U811-WIN