ACI SC Leak Detection Sensing Cable

Features

  • Detects any conductive fluid
  • Designed to eliminate false alarms
  • Fast drying; quickly resets to detect the next leak
  • Plenum (CL2P) rated
  • Durable yet flexible design
  • Patented since 2000
  • Available in standard and custom lengths with pre-installed twist-lock connectors
Enquiry
Category:

Automation Components, Inc. (ACI) creates, manufactures, and distributes building automation sensors for the heating, ventilation, and air conditioning (HVAC) Industry. Dpstar is ACI Authorised Distributor in Malaysia. Our product lines include Temperature Sensors, Relative Humidity Sensors, Current Sensors, Pressure Sensors, Gas Sensors, and Wireless Sensors.

ACI Leak Detection Sensing Cable is patented protection from even the smallest leaks. ACI’s sensing cable (SC) reliably detects water and other
conductive fluid leaks, protecting facilities from damage and downtime.

What Sets the SC Series Sensing Cable Apart?

  • Encapsulate at-risk areas and sources of leaks. Conductive fluid contact at any point along the length of the cable triggers an alarm condition.
  • Engineered for reliability. Sensing wires are covered with a non-conductive polymer mesh; dirt, dust, and contact with metal will not generate false alarms.
  • Constant oversight. Four-wire construction allows the system to continually monitor the cable and identify damaged or disconnected cables.

Dimension

Applications

  • Place around the perimeter of rooms.
  • Serpentine under raised floors
  • Install inside drop ceilings
  • Affix to the bottom of pipes
  • Secure around floor drains and under plumbing fixtures
  • Encapsulate storage tanks and cooling equipment

Specification

Plenum Rating CL2P (UL)
Sheer Strength >180 lbs. (>81.65kg)
Cut Through Resistance >40 lbs. (>18.14kg) with.005in (0.127mm) blade
Abrasion Resistance 60 cycles per UL 719
Connector 4 pin, 0.96in (24.38mm) diameter
Diameter of Cable Not to exceed 0.25in (6.35mm)
Operating Environment
(Temperature, Humidity, Altitude)
32° to 167°F (0° to 75°C) 5% to 95% RH, non-condensing 15,000ft (4,572m) max.
Storage Environment -22° to 185°F (-30° to 85°C)
Weight .02lbs./ft (29.74g/m)
Certifications CE; UL CL2P; RoHS Compliant; Plenum Rated; Patent No. 6,144,209