Compact RTD Temperature Transmitter – PR Electronics 5802

Features

– RTD or Ohm input
– Accuracy: Better than 0.1% of selected range
– 2- / 3-wire RTD connection
– Programmable sensor error value
– Output 4…20 mA, with or without M12 connector

Enquiry

Application

  • Linearized temperature measurement with Pt100…Pt1000, or Ni100…Ni1000 sensor.
  • Conversion of linear resistance variation to a standard analog current signal.

Technical characteristics

  • Within a few seconds the user can program PR5802 to measure temperatures within all RTD ranges defined by the norms.
  • The RTD and resistance inputs have cable compensation for 3-wire connection.

Mounting / installation

  • For tube mounting, e.g. M18 barrel housing or customer specific housing.
  • The unit is tested with an M12 connector, mounted in a steel housing and molded with Silgel 612 silicone molding compound. This is PR electronics’ recommended method to comply with specifications and EMC data.

Specification

ENVIRONMENTAL CONDITIONS
Operating temperature -40°C to +85°C
Storage temperature -40°C to +85°C
Relative humidity < 95% RH (non-cond.)
MECHANICAL SPECIFICATIONS
Dimensions, PCB only (WxHxD) 5.0 x 15.50 x 38.0 mm
Dimensions (incl. M12 connector) 9.5 x 15.50 x 47.70 mm
Weight approx. 2.65 g 5802A1xx 4.05 g 5802A2xx
COMMON SPECIFICATIONS
Supply
Supply voltage 8.0…35 VDC
Internal power dissipation 25 mW…0.8 W
Response time
Response time (programmable) 0.33…60 s
Voltage drop 8.0 VDC
Warm-up time 5 min.
Programming Loop Link
Signal / noise ratio Min. 60 dB
Signal dynamics, input 19 bit
Signal dynamics, output 16 bit
Effect of supply voltage change < 0.005% of span / VDC
Accuracy Better than 0.1% of sel. range
EMC immunity influence < ±0.5% of span
INPUT SPECIFICATIONS
RTD input
RTD type Pt100, Ni100, lin. R
Cable resistance per wire 10 Ω (max.)
Sensor current > 0.2 mA, < 0.4 mA
Effect of sensor cable resistance (3-wire) < 0.002 Ω / Ω
Sensor error detection Yes
Common input specifications
Max. offset 50% of selected max. value
OUTPUT SPECIFICATIONS
Common output specifications
Updating time 135 ms
Current output
Signal range 4…20 mA
Min. signal range 16 mA
Load (@ current output) ≤ (Vsupply – 8) / 0.023 [Ω]
Load stability ≤ 0.01% of span / 100 Ω
Sensor error indication Programmable 3.5…23 mA
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA
of span = of the presently selected range
OBSERVED AUTHORITY REQUIREMENTS
RoHS 2011/65/EU

Download

PR Electronic 5802 Compact RTD temperature transmitter- isolated-DpstarGroup