Evikon E2648-LEL Combustible Gases Detector Transmitter

Features

  • Accurate and stable measurement
  • Industrial IP66 wall mount housing
  • Two analog outputs settable to 4-20 mA or 0-10 V
  • RS485 Modbus RTU digital interface
  • Two relays for alarm / ventilation control (option)
  • Attached or remote senso
Enquiry
Category:

Dpstar is an authorized distributor of Evikon. Evikon is an instrumentation company, specializing in the development, manufacturing, and marketing of sensor-based electronic measurement instruments for industrial and building automation applications. Our mission is to provide businesses and organizations with convenient and efficient technical solutions for the measurement of environmental parameters and control of processes – temperature, pressure, level, humidity, and moisture, toxic and explosive gases – to help save resources, increase production quality and ensure safety.

Combustible gas detector-transmitter E2648-LEL is a member of new PluraSens® family of multifunctional measurement instruments. The transmitter exhibits sensitivity to hydrogen, methane, acetylene, propane and butane. The instrument utilises a fully calibrated metal-oxide semiconductor gas sensor with excellent repeatability, stability and long lifetime. Two relays with closing contact (optional) may be used for remote signalling or concentration control. Two alarm set-points are user settable. Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.

Dimension

Applications

  • Underground parkings
  • Boiler houses
  • Battery charging rooms
  • Kitchens
  • and other confined spaces, where potentially explosive concentration of combustible gases can accumulate.

Specification

Detected gases hydrogen, methane, acetylene, propane, butane
Default calibration methane CH4
Sensor type metal-oxide semiconductor
pellistor (catalytic bead) on demand
Sampling method diffusion
Detection range 0…100% LEL
Resolution 0,1% LEL
Accuracy ± 2% LEL
Sensor lifetime > 5 years
Power supply 12…36 VDC (default),
24 VAC or 230 VAC as options
Digital interface RS485, Modbus RTU protocol
Analog outputs 2 × 4-20 mA / 0-10 V, user settable
Output relays (option) 2 × SPST relays (closing contact),
250 VAC / 30 VDC, 5 A max
Default alarm set-points 20% LEL / 50% LEL CH4
Enclosure die-cast aluminium, wall mount, IP66
Dimensions H120 × W125 × D57 mm
Operating conditions -40…+70 °C, 15…90 %RH