Evikon E2658-SO2 Flameproof Sulfur Dioxide Detector Transmitter

Features

  • Wall mount robust flameproof metal enclosure
  • Suitable for ATEX Zones 2 and 22
  • Two analog outputs settable to 4-20 mA or 0-10 V
  • RS485 Modbus RTU digital interface
  • Relay option
Enquiry
Category:

Dpstar is an authorized distributor of Evikon. Evikon is an instrumentation company, specializing in the development, manufacturing, and marketing of sensor-based electronic measurement instruments for industrial and building automation applications. Our mission is to provide businesses and organizations with convenient and efficient technical solutions for the measurement of environmental parameters and control of processes – temperature, pressure, level, humidity, and moisture, toxic and explosive gases – to help save resources, increase production quality and ensure safety.

E2658 series is a new line of flameproof detectors and transmitters intended for use in ATEX Zones 2 and 22.  E2658 series devices are based on PluraSens® multifunctional platform. Sulfur dioxide detector-transmitter E2658-SO2 utilises a fully calibrated and temperature compensated electrochemical gas sensor with excellent repeatability, stability and long lifetime. Two relays with closing contact (optional) may be used for remote signalling or concentration control. Two alarm set-points are user settable. Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.

Dimension

Specification

Calibration sulfur dioxide SO2
Sensor type electrochemical
Sampling method diffusion
Detection range 0…50 ppm SO2
0…2000 ppm SO2
Resolution 0,1 ppm SO2 for 50 ppm range
1,5 ppm SO2 for 2000 ppm range
Sensor lifetime > 2 years
Power supply 12…36 VDC (default),
24 VAC or 230 VAC as options
Digital interface RS485, Modbus RTU protocol
Analog outputs 2 × 4-20 mA / 0-10 V, user settable
Output relays (option) 2 × SPST relays (closing contact),
250 VAC / 30 VDC, 5 A max
Enclosure die-cast aluminium, wall mount, IP66
Dimensions H80 × W125 × D57 mm
Operating conditions -30…+50 °C, 15…90 %RH
safe areas and ATEX Zones 2 and 22