PR Electronics 5104B – Ex Repeater / Power Supply

Features

  • 1- or 2-channel version
  • 3- / 5-port 3.75 kVAC galvanic isolation
  • Loop supply > 17.1 V in hazardous area
  • 20 programmable measurement ranges
  • Universal supply by AC or DC
Enquiry
Category:

PR Electronics 5104B – Ex Repeater / Power Supply

Application

  • Provides power and safety isolation for 2-wire transmitters installed in hazardous areas.
  • Acts as a safety barrier for analog current/voltage signals originating from hazardous areas.
  • Allows for 1:1 signal conversion or signal conditioning of analog current/voltage signals.

Technical Specifications

  • PR Electronics 5104B offers 20 pre-calibrated measurement ranges selectable via internal DIP switches, eliminating the need for recalibration. Custom ranges are also available.
  • PR Electronics PR5104B employs microprocessor technology for precise gain and offset adjustment, ensuring a response time of less than 25 ms for analog signal transmission.
  • Inputs, outputs, and power supply are electrically isolated and floating.
  • The output can function as either an active current/voltage transmitter or a 2-wire transmitter.

Mounting/Installation

  • Mounts vertically or horizontally on a DIN rail. With the 2-channel version, up to 84 channels can be mounted per meter.
  • Note: PR Electronics 5104B is recommended as an intrinsically safe (I.S.) barrier for 5331D, 5333D, 5334B, 5343B, 6331B, 6333B, and 6334B models.

Specification

ENVIRONMENTAL CONDITIONS
Operating temperature -20°C to +60°C
Calibration temperature 20…28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
MECHANICAL SPECIFICATIONS
Dimensions (HxWxD) 109 x 23.5 x 130 mm
DIN rail type DIN 46277
Weight approx. 225 g
Wire size 1 x 2.5 mm2 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2…13.2 Hz ±1 mm
13.2…100 Hz ±0.7 g
COMMON SPECIFICATIONS
Supply
Supply voltage, universal 21.6…253 VAC, 50…60 Hz or 19.2…300 VDC
Fuse 400 mA SB / 250 VAC
Max. required power ≤ 3 W (2 channels)
Internal power dissipation ≤ 2 W (2 channels)
Isolation voltage
Isolation voltage, test / working 3.75 kVAC / 250 VAC
PELV/SELV IEC 61140
Auxiliary supplies
2-wire supply (pin 44…42 and 54…52) 28…17.1 VDC / 0…20 mA
Response time
Response time (0…90%, 100…10%) < 25 ms
Signal / noise ratio Min. 60 dB (0…100 kHz)
Accuracy Better than 0.1% of sel. range
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span
INPUT SPECIFICATIONS
Common input specifications
Max. offset 20% of max. value
Current input
Measurement range 0…20 mA
Min. measurement range (span) 16 mA
Input resistance Nom. 10 Ω + PTC 10 Ω
Voltage input
Measurement range 0…10 VDC
Min. measurement range (span) 8 VDC
Input resistance > 2 MΩ
OUTPUT SPECIFICATIONS
Current output
Signal range 0…20 mA
Min. signal range 16 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Current limit ≤ 28 mA
Passive 2-wire mA output
Effect of external 2-wire supply voltage variation < 0.005% of span / V
Voltage output
Signal range 0…1 VDC / 0…10 VDC
Min. signal range 0.8 VDC / 8 VDC
Load (@ voltage output) ≥ 500 kΩ
External loop supply 29 VDC
of span = of the presently selected range
OBSERVED AUTHORITY REQUIREMENTS
EMC 2014/30/EU
LVD 2014/35/EU
EAC TR-CU 020/2011
APPROVALS
ATEX DEMKO 99ATEX126013, II (1) GD [EEx ia] IIC
UL UL 913, UL 508
EAC Ex RU C-DK.HA65.B.00355/19
DNV-GL Marine Stand. f. Certific. No. 2.4

Download