PR Electronics 5531B Loop-Powered LCD Indicator

Features

  • 4 digit 1/8 DIN (48 x 96 mm) loop-powered LCD display
  • Easy push-button configuration
  • Backlit LCD display is readable in low light conditions
  • Display can be mounted in the safe area or in I.S. / Ex zone
Enquiry
Category:

PR Electronics 5531B Loop-Powered LCD Indicator is designed for remote display of process loops, powered directly by the 4 to 20 mA current loop. It offers ease of scaling to display the correct process value without the need for separate power wiring, making it ideal for hazardous areas such as Ex Zone 1.

Applications

  • Remote Process Display: Perfect for remote display of process loops, eliminating the need for separate power wiring.
  • Hazardous Area Installation:
    • 5531B: Suitable for mounting in Ex Zone 1.
    • 5531B1 Ex Display: Includes the 8501 enclosure and can be mounted in Ex Zone 2 or 22 (gas or dust).
    • 5531B2 Ex Display: Includes the 8501 enclosure and can be mounted in Ex Zone 1, 2, 21, or 22 (gas or dust).

Technical Characteristics

  • Wide Measurement Range: Compliant with NAMUR NE43, with a full measurement range of 3.6 to 23 mA.
  • Scalable Display: The display can be push-button scaled to any range between -9999 to 9999, with the option for reverse display action.
  • Adjustable Backlight: The LCD backlight can be set to half or full intensity for easy viewing in low light conditions.
  • Low Power Requirement: Requires only 1.5 VDC (75 Ω loop load) with the backlight turned off.
  • HART Transparent: The input is HART transparent, ensuring compatibility with HART communication.
  • Tamper Protection: Front push-buttons can be disabled to prevent unauthorized adjustments.

Mounting / Installation

  • Panel Mounting: Once panel mounted with the included gasket, the 5531B provides IP65 ingress protection, ensuring durability and protection against dust and water ingress.
  • Enclosure Options: The 8501 enclosure enhances protection and suitability for different Ex zones.

PR Electronics 5531B Loop-Powered LCD Indicator is an ideal solution for industries requiring accurate and reliable remote display of process values in hazardous areas. Its ease of installation, scalable display, and low power requirements make it a versatile choice for various applications.

Specification

ENVIRONMENTAL CONDITIONS
Operating temperature -20°C to +60°C
Storage temperature -20°C to +60°C
Calibration temperature 20…28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP65, from front
MECHANICAL SPECIFICATIONS
Dimensions (HxWxD) 48 x 96 x 120 mm
Cut out dimensions 44.5 x 91.5 mm
Weight approx. 200 g
Cable glands and cable diameter M16 x 1.5 / Ø 5…8 mm
Wire size, connector terminal 1 – 4 0.13…2.08 mm2 / AWG 26…14 stranded wire
COMMON SPECIFICATIONS
Supply
Supply voltage Input loop-powered
Response time
Response time (0…90%, 100…10%) < 1 s
EMC immunity influence < ±0.5% of span
Signal / noise ratio > 60 dB
Updating time 500 ms
INPUT SPECIFICATIONS
Current input
Measurement range 3.6…23 mA
Loop error detection, 4…20 mA: Low ~ < 3 mA
Loop error detection, 4…20 mA: High ~ > 24 mA
Input voltage drop, without backlight < 1.5 V @ 20 mA
Input voltage drop, with full backlight < 10.5 V @ 20 mA
OUTPUT SPECIFICATIONS
Display
Display readout ± 9999 (4 digits)
Digit height 16 mm
OBSERVED AUTHORITY REQUIREMENTS
EMC 2014/30/EU
EAC TR-CU 020/2011
APPROVALS
ATEX KEMA 05ATEX1044 X (5531A/B1) KEMA 05ATEX1105 X (5531B/B2)
EAC Ex RU C-DK.HA65.B.00355/19

Download

PR Electronics 5531B Loop-Powered LCD Indicator-DpstarGroup