PR Electronics 9410 Power Control Unit

Features

  • Distributes supply voltage to the power rail
  • Optional connection of backup supply
  • Approved for installation in I.S. / Ex zone 2 / Div. 2
  • Optional redundant supply for the power rail
  • Must be installed on power rail, PR type 9400
Enquiry
Category:

PR Electronics 9410 Power Control Unit is designed to monitor and manage power supply to devices mounted on the power rail. It detects errors and transmits a collective alarm to the control system, ensuring reliable and continuous operation. It also supports redundant power supply configurations for enhanced reliability.

Application and Advanced Features

  • Error Detection and Alarm: Detects errors from devices mounted on the power rail and transmits a collective alarm to the control system via the internal status relay.
  • Dual Power Supply Connection: Supports optional connection of two power supplies – a primary supply and a backup supply.
  • Redundant Supply: Redundant supply for the power rail can be achieved by mounting two 9410 units connected to two separate power supplies (e.g., PR no. 9421).

Technical Characteristics

  • Status Relay Conditions: The status relay will be energized when the following conditions are met:
    • Supply voltage is present on pins 31 and 32.
    • Backup supply voltage is present on pins 34 and 33. (If the backup supply is not in use, a jumper must be placed between pins 32 and 33 – the jumper is delivered with the device).
    • There are no error messages from the devices connected to the power rail.
  • Collective Alarm Activation: When a collective alarm is activated via the power rail, the status relay in the 9410 will be de-energized (pins 11, 12, and 13).
  • LED Indicators:
    • Two green front LEDs indicate the connection of the primary supply and backup supply.
    • A red LED indicates error status.

PR Electronics 9410 Power Control Unit is an essential component for ensuring reliable power management and error detection in systems utilizing a power rail. Its advanced features and robust design make it suitable for maintaining continuous and fault-tolerant operation in industrial environments.

Specification

ENVIRONMENTAL CONDITIONS
Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II
MECHANICAL SPECIFICATIONS
Dimensions (HxWxD) 109 x 23.5 x 104 mm
Weight approx. 140 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13…2.08 mm2 AWG 26…14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2…13.2 Hz ±1 mm
13.2…100 Hz ±0.7 g
COMMON SPECIFICATIONS
Supply
Max. required power 96 W
Internal power dissipation 2 W (max.)
Efficiency > 97.9%
INPUT SPECIFICATIONS
Supply voltage 21.6…26.4 VDC (double / reinforced isolation)
Backup supply 21.6…26.4 VDC
OUTPUT SPECIFICATIONS
Status relay
Max. voltage 250 / 30 VDC
Max. current 2 AAC / 2 ADC
Max. AC power 500 VA / 60 W
Output voltage Input voltage-0.5 VDC (@ 4 A)
Output power 96 W (max.)
Output current 4 A (max.)
Output ripple Same as input ripple
OBSERVED AUTHORITY REQUIREMENTS
EMC 2014/30/EU
LVD 2014/35/EU
ATEX 2014/34/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011
EAC LVD TR-CU 004/2011
APPROVALS
ATEX KEMA 07ATEX0152 X
IECEx KEM 08.0025X
c FM us FM19US0056X /FM19CA0029X
INMETRO DEKRA 16.0007 X
c UL us, UL 61010-1 E314307
c UL us, UL 913 E233311 (only 9410-U9)
EAC Ex RU C-DK.HA65.B.00355/19
DNV-GL Marine TAA00000JD
ClassNK TA18527M

Download

PR Electronic 9410 Power control unit-DpstarGroup