PR Electronics 5714 Programmable LED Indicator

Features

  • 4-digit 14-segment LED display
  • Input for mA, V, Ohm, RTD, TC and potentiometer
  • 2 relays and analog output
  • Universal supply
  • Front key programmable
Enquiry
Category:

PR Electronics 5714 Programmable LED Indicator is designed for digital readout of various signals, including current, voltage, resistance, temperature, and potentiometer signals. It offers robust process control capabilities with two potential-free relays and an optional analog output, making it suitable for local readout in extremely wet atmospheres with an optional splash-proof cover.

Applications

  • Digital Signal Display: Provides digital readout for current, voltage, resistance, temperature, and potentiometer signals.
  • Process Control: Equipped with two potential-free relays and/or an analog output for advanced process control.
  • Wet Environments: Ideal for local readout in extremely wet atmospheres when used with the specially designed splash-proof cover.

Technical Characteristics

  • 4-Digit LED Display: Features a 4-digit LED indicator with 13.8 mm 14-segment characters. Maximum display readout ranges from -1999 to 9999, with a programmable decimal point and relay ON/OFF indication.
  • Customizable Parameters: All standard operational parameters can be adjusted via the front function keys to suit any application.
  • Multilingual Help Texts: Help texts are available in eight languages, selectable via a menu item.
  • Fully Configured Options: Available fully-configured according to specifications for immediate process control and visualization.
  • Galvanic Isolation: Inputs, outputs, and supply are floating and galvanically separated, ensuring robust isolation and signal integrity.
  • Relay Output Testing: In versions with relay outputs, installation test time can be minimized by independently activating/deactivating each relay regardless of the input signal.

Mounting / Installation

  • Panel Mounting: Designed for mounting in the panel front. The included rubber packing must be installed between the panel cutout hole and the display front to achieve IP65 (type 4X) protection.
  • Splash-Proof Cover: For extra protection in extreme environments, the PR5714 can be delivered with an optional specially designed splash-proof cover.

PR Electronics 5714 Programmable LED Indicator is an excellent choice for industries requiring precise digital readout and advanced process control capabilities, particularly in challenging environments. Its robust design, customizable parameters, and reliable performance make it suitable for a wide range of applications.

Specification

ENVIRONMENTAL CONDITIONS
Operating temperature -20°C to +60°C
Calibration temperature 20…28°C
Relative humidity < 95% RH (non-cond.)
Protection degree (mounted in panel) IP65 / Type 4X
MECHANICAL SPECIFICATIONS
Dimensions (HxWxD) 48 x 96 x 120 mm
Cut out dimensions 44.5 x 91.5 mm
Weight approx. 230 g
Wire size, pin 41-46 (max.) 0.05…1.31 mm2 AWG 30…16 stranded wire
Wire size, others, max. 0.05…3.31 mm2 / AWG 30…12 stranded wire
Vibration IEC 60068-2-6
2…13.2 Hz ±1 mm
13.2…100 Hz ±0.7 g
COMMON SPECIFICATIONS
Supply
Supply voltage, universal 21.6…253 VAC, 50…60 Hz or 19.2…300 VDC
Max. required power 2.5 W (5714A) 3.0 W (5714B/C)
3.5 W (5714D)
Internal power dissipation 2.2 W (5714A) 2.7 W (5714B/C)
3.2 W (5714D)
Isolation voltage
Isolation voltage, test / working 2.3 kVAC / 250 VAC
Response time
Temperature input, programmable (0…90%, 100…10%) 1…60 s
mA / V input (programmable) 0.4…60 s
Auxiliary supplies
2-wire supply (pin 46…45) 25…15 VDC / 0…20 mA
Signal / noise ratio Min. 60 dB (0…100 kHz)
Accuracy Better than 0.1% of sel. range
EMC immunity influence < ±0.5% of readout
INPUT SPECIFICATIONS
RTD input
RTD type Pt10/20/50/100/200/250; Pt300/400/500/1000; Ni50/100/120/1000; Cu10/20/50/100
Cable resistance per wire 50 Ω (max.)
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Linear resistance input
Linear resistance min….max. 0 Ω…10000 Ω
Potentiometer input
Potentiometer min….max. 10 Ω…100 kΩ
TC input
Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
CJC via int. mounted sensor ±(2.0°C + 0.4°C * Δt)
Δt = Internal temp.-ambient temp.
Sensor error detection Yes
Sensor error current: When detecting / else Nom. 2 μA / 0 μA
Current input
Measurement range 0…23 mA
Programmable measurement ranges 0…20 and 4…20 mA
Input resistance Nom. 20 Ω + PTC 25 Ω
Sensor error detection Loop break 4…20 mA
Voltage input
Measurement range 0…12 VDC
Programmable measurement ranges 0/0.2…1; 0/2…10 VDC
Input resistance Nom. 10 MΩ
OUTPUT SPECIFICATIONS
Display
Display readout -1999…9999 (4 digits)
Decimal point Programmable
Digit height 13.8 mm
Display updating. 2.2 times / s
Input outside input range is indicated by Explanatory text
Current output
Signal range 0…23 mA
Programmable signal ranges 0…20/4…20/20…0/20…4 mA
Load (@ current output) ≤ 800 Ω
Load stability ≤ 0.01% of span / 100 Ω
Sensor error indication 0 / 3.5 / 23 mA / none
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA
Output limitation, on 4…20 and 20…4 mA signals 3.8…20.5 mA
Output limitation, on 0…20 and 20…0 mA signals 0…20.5 mA
Current limit ≤ 28 mA
Relay output
Relay functions Setpoint
Hysteresis 0…100%
ON and OFF delay 0…3600 s
Sensor error reaction Break / Make / Hold
Max. voltage 250 VAC / VDC
Max. current 2:00 AM
Max. AC power 500 VA
Max. DC current, resistive load ≤ 30 VDC 2 ADC
Max. DC current, resistive load > 30 VDC See manual for details
OBSERVED AUTHORITY REQUIREMENTS
EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
APPROVALS
DNV-GL Marine Stand. f. Certific. No. 2.4
EU RO Mutual Recognition Type Approval MRA000000Z
UL UL 508 / C22.2 no. 14

Download