Ratio & Bias Setter – Shimaden CP2SR Series

Enquiry

Outputs after multiplying input signal by ratio. Bias values can also be set. Isolation for input/output is provided as standard feature. 6 toxic substances, which are subject to RoHS regulations, are contained. However, the amount of toxic substances contained does not exceed standardized values.

Specification

Input DC Voltage or Current (Refer to “Ordering Information”.)
Output DC Voltage or Current (Refer to “Ordering Information”.)
Ratio setting range 0.3–3 times
Bias Value Setting Range -100 –100%
Setting Precision ±0.5% of the input range (for set value monitor output) at 23°C
Calculation Precision ±0.5%FS (when ratio = 1, bias value = 0%) at 23°C
Operation l0 = nl1  I0: Output signal (%)  n: Ratio
l0 = nl1±α  l1: Input signal (%)  α: Bias (%)
When the operation result exceeds the output range, a correct signal will not be output.
Monitor Output Voltage Ratio: 0.3–3 times / 0.3–3V (Load resistance: 5 kΩ min.)
Bias: -100–100% / -1–1V (Load resistance: 5 kΩ min.)
Isolation Insulation between inputs and outputs
Influence of Ambient Temperature ±0.2% FS for temperature change of 10 °C
Response Time 200 msec. max. (0–90%)
Repeatability ±0.1% of input range

Ordering Information

ITEMS CODE SPECIFICATIONS
SERIES CP2SR- Ratio & Bias Setter
Input 3   0–1V DC / FS Input Resistance: 1MΩ
4   0–10V DC / FS Input Resistance: 1MΩ
5   1–5V DC / FS Input Resistance: 1MΩ
6   4–20mA DC / FS Receiving Impedance: 62Ω
9   Others (Please consult before ordering.)
Output 3   0–1V DC / FS Max. Current: 2mA
4   0–10V DC / FS Max. Current: 2mA
5   1–5V DC / FS Max. Current: 2mA
6   4–20mA DC / FS Load Resistance: 600Ω max.
9   Others (Please consult before ordering.)
POWER SUPPLY 02-   24V DC±10%
13-   100–110V AC±10% 50/60Hz
14-   110–120V AC±10% 50/60Hz
15-   200–220V AC±10% 50/60Hz
16-   220–240V AC±10% 50/60Hz
99-   Others (Please consult before ordering.)
REMARKS 0  Without