Smart Pressure Transmitter – Aplisens APCE-2000PD Series

Features

  • 4…20 m A ou tput signal + HART protocol
  • ATEX Intrinsic safety
  • Accuracy 0.1 %
  • Rangeability 1 00:1
  • Gold plated diaphragm (Au)
Enquiry

The APCE-2000 pressure transmitter is applicable to the measurement of the pressure, underpressure or absolute pressure of gases, vapours and liquids. The active sensing element is a piezoresistant silicon sensor separated from the medium by a diaphragm and by specially selected type of manometric liquid.

The data interchange with the transmitter enables users to:

  • identify the transmitter
  • configure the output parameters:
    – measurement units and the values of the start points and end points at the measurement range
    – damping time constant
    – conversion characteristic (inversion, user’s non-linear characteristic)
  • read the currently measured pressure value of the output current and the percentage output control level
  • force an output current with a set value
  • calibrate the transmitter in relation to a model pressure

Specification

Metrological parameters
Accuracy ≤ ±0,1% of the calibrated range
Long-term stability
(for the basic range)
≤ accuracy for 3 years
or ≤ 2 x accuracyfor 5 years
HS version: ≤ accuracy for 6 years
or ≤ 2 x accuracyfor 10 years
Thermal error < ±0,08% (FSO) / 10°C
0,1% for ranges no. 16÷19)
max. ±0,25% (FSO) in the whole compensation range
(0,4%for ranges16÷19)
Thermal compensation range -25…80°C
Special version: -40…80°C
Response time 16…230ms(programmable)
Additional electronic damping 0…60s
Error due to supply voltage changes 0,002% (FSO) / V
Electrical parameters
Power supply 7,5…55 VDC (Ex ia 7,5…30VDC)
Output signal 4…20 mA+ HART
Resistance required for communication min. 240Ω
Materials SS316L, Hastelloy C 276, Au
Wetted parts and diaphragms
Casing SS304
Operating conditions
Operating temperature range (ambient temp.) -40…85°C
Ex version -40…80°C
Medium temperature range -40…120°C
over 120°C measurement with use an impulse line
or diaphragm seals
up to 100°C PED version
CAUTION: the medium must not be allowed to freeze in the impulse line or close to the process connection of the transmitter