PR Electronics 9203B – Solenoid / Alarm Driver

Features

  • Universal Ex driver for solenoids, acoustic alarms and LEDs
  • Extended self-diagnostics
  • 1 or 2 channels
  • Can be supplied separately or installed on power rail, PR 9400
  • SIL 2-certified via Full Assessment
Enquiry
Category:

PR Electronics 9203B – Solenoid / Alarm Driver

Advanced features

  • The device features a universal intrinsically safe (I.S.) driver capable of controlling solenoids and similar devices, supporting various I.S. data through three integrated I.S. barriers.
  • Two hardware configurations offer a choice between Low (35 mA) and High (60 mA) current outputs.
  • Configuration and monitoring are facilitated via a detachable display front (PR 45xx).
  • Each channel can be set to operate in direct or inverted mode using the PR 45xx interface, with the option to adjust output current to suit hazardous area requirements.
  • Optional monitoring of output current to the hazardous area is available through PR 45xx.
  • Redundant power supply options include power rail and/or separate supply.

Application:

  • PR Electronics 9203B can be installed in safe areas or Zone 2 / Class 1, Division 2 areas, transmitting signals to Zone 0, 1, 2 and Zone 20, 21, 22, including M1 mining / Class I/II/III, Div. 1, Gr. A-G.
  • It serves as a driver for controlling ON/OFF solenoids, acoustic alarms, and LEDs in safe or hazardous areas.
  • Control inputs include NPN/PNP signals or switch signals.
  • Internal error events can be monitored via individual status relays or a collective electronic signal via the power rail.
  • PR Electronics 9203B is designed, developed, and certified for SIL 2 applications according to IEC 61508 standards.
  • It is suitable for systems up to Performance Level “d” according to ISO-13849.

Technical Characteristics:

  • Front indicators include 1 green LED and 2 yellow/red LEDs to indicate operational status and malfunctions.
  • Galvanic isolation of 2.6 kVAC between input, output, and supply ensures safety.

Mounting:

  • The devices support vertical or horizontal mounting without requiring distance between adjacent units.

Specification

ENVIRONMENTAL CONDITIONS
Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20…28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II
MECHANICAL SPECIFICATIONS
Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501/451x 109 x 23.5 x 116 / 131 mm
Weight approx. 170 g
Weight incl. 4501 / 451x (approx.) 185 g / 200 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13…2.08 mm2 AWG 26…14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2…13.2 Hz ±1 mm
13.2…100 Hz ±0.7 g
COMMON SPECIFICATIONS
Supply
Supply voltage 19.2…31.2 VDC
Fuse 1.25 A SB / 250 VAC
Max. required power ≤ 1.9 W / ≤ 3.1 W (1 / 2 ch.) – low current ≤ 2.5 W (1 ch.) – high current
Max. power dissipation, 1 / 2 ch. ≤ 1.1 W / ≤ 1.7 W – low current
Max. power dissipation ≤ 1.7 W (1 ch.) – high current
Isolation voltage
Test /working: Input to any 2.6 kVAC / 300 VAC reinforced isolation
Output 1 to output 2 1.5 kVAC / 150 VAC reinforced isolation
Status relay to supply 1.5 kVAC / 150 VAC reinforced isolation
Programming PR 45xx
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span
INPUT SPECIFICATIONS
NPN and mechanical switch
Trig level LOW ≤ 2.0 VDC
Trig level HIGH ≥ 4.0 VDC
Max. external voltage 28 VDC
Input impedance 3.5 kΩ
PNP
Trig level LOW ≤ 8.0 VDC
Trig level HIGH ≥ 10.0 VDC
Max. external voltage 28 VDC
Input impedance 3.5 kΩ
OUTPUT SPECIFICATIONS
Status relay
Max. voltage 125 VAC / 110 VDC
Max. current 0.5 AAC / 0.3 ADC
Max. AC power 62.5 VA / 32 W
Output ripple < 40 mVRMS
OBSERVED AUTHORITY REQUIREMENTS
EMC 2014/30/EU
LVD 2014/35/EU
ATEX 2014/34/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011
APPROVALS
ATEX KEMA 07ATEX0147 X
IECEx KEM 09.0001X
c FM us FM19US0057X / FM19CA0030X
INMETRO DEKRA 16.0006 X
c UL us, UL 61010-1 E314307
c UL us, UL 913 E233311 (only 9203xxxx-U9)
EAC Ex RU C-DK.HA65.B.00355/19
DNV-GL Marine TAA00000JD
ClassNK TA18527M
SIL SIL 2 certified & fully assessed acc. to IEC 61508