PR Electronics 9113A – Temperature / Ma Converter

Features

  • Input for RTD, TC and mA
  • Active / passive mA output via the same two terminals
  • 1 or 2 channels
  • Can be supplied separately or installed on power rail, PR type 9400
  • SIL 2-certified via Full Assessment
Enquiry

PR Electronics 9113A – Temperature / Ma Converter

Advanced features

  • Configuration and monitoring are facilitated through a detachable display front (PR Electronics 45xx), allowing for process calibration and signal simulation.
  • Configuration settings can be copied from one device to others of the same type using the display front.
  • For enhanced accuracy, TC inputs can utilize either the internal Cold Junction Compensation (CJC) or a terminal featuring a built-in PT100 sensor (PR Electronics 5910 for channel 1 / PR Electronics 5913 for channel 2).
  • Provides advanced monitoring of internal communication and stored data.
  • Optional SIL 2 functionality that requires activation through a menu option.

Application

  • PR Electronics 9113Axx model can be installed in safe areas or in Zone 2 / Class I, Division 2, Groups A, B, C, D.
  • Capable of converting and scaling temperature (Pt, Ni, and TC) and active current signals.
  • Designed, developed, and certified for SIL 2 applications as per IEC 61508 requirements.
  • Suitable for use in systems up to Performance Level “d” according to ISO-13849.

Technical Characteristics

  • Operational status and malfunction are indicated by 1 green and 2 red LEDs on the front panel.
  • Offers 2.6 kVAC galvanic isolation between input, output, and power supply.

Mounting

  • Devices can be mounted either vertically or horizontally with no requirement for spacing between adjacent units.

Specification

ENVIRONMENTAL CONDITIONS
Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20…28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II
MECHANICAL SPECIFICATIONS
Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501/451x 109 x 23.5 x 116 / 131 mm
Weight approx. 250 g
Weight incl. 4501 / 451x (approx.) 265 g / 280 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13…2.08 mm2 AWG 26…14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2…13.2 Hz ±1 mm
13.2…100 Hz ±0.7 g
COMMON SPECIFICATIONS
Supply
Supply voltage 19.2…31.2 VDC
Fuse 400 mA SB / 250 VAC
Max. required power ≤ 0.8 W/≤ 1.4 W (1 ch./2 ch.)
Max. power dissipation, 1 / 2 ch. ≤ 0.8 W / ≤ 1.4 W
Isolation voltage
Test /working: Input to any 2.6 kVAC / 300 VAC reinforced isolation
Analog output to supply 2.6 kVAC / 300 VAC reinforced isolation
Status relay to supply 1.5 kVAC / 150 VAC reinforced isolation
Response time
Temperature input, programmable (0…90%, 100…10%) 1…60 s
mA / V input (programmable) 0.4…60 s
Programming PR 45xx
Signal / noise ratio Min. 60 dB (0…100 kHz)
Signal dynamics, input 24 bit
Signal dynamics, output 16 bit
Accuracy Better than 0.1% of sel. range
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span
INPUT SPECIFICATIONS
RTD input
RTD type Pt10/20/50/100/200/250/300/Pt400/500/1000; Ni50/100/120/1000
Cable resistance per wire 50 Ω (max.)
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Programmable ON / OFF
TC input
Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) via ext. sensor in 5910 20…28°C ≤ ±1°C, -20…20°C / 28…70°C ≤ 2°C
CJC via int. mounted sensor ±(2.0°C + 0.4°C * Δt)
Δt = Internal temp.-ambient temp.
Sensor error detection Programmable ON or OFF (only wire breakage)
Sensor error current: When detecting / else Nom. 2 μA / 0 μA
Current input
Measurement range 0…23 mA
Programmable measurement ranges 0…20 and 4…20 mA
Input resistance Nom. 20 Ω + PTC 50 Ω
Sensor error detection Programmable ON / OFF
OUTPUT SPECIFICATIONS
Current output
Signal range 0…23 mA
Programmable signal ranges 0…20/4…20/20…0/20…4 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Sensor error indication 0 / 3.5 / 23 mA / none
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA
Output limitation, on 4…20 and 20…4 mA signals 3.8…20.5 mA
Output limitation, on 0…20 and 20…0 mA signals 0…20.5 mA
Current limit ≤ 28 mA
Passive 2-wire mA output
Max. external 2-wire supply 26 VDC
Max. load resistance [Ω] (Vsupply-3.5)/0.023 A
Effect of external 2-wire supply voltage variation < 0.005% of span / V
Status relay
Max. voltage 125 VAC / 110 VDC
Max. current 0.5 AAC / 0.3 ADC
Max. AC power 62.5 VA / 32 W
of span = of the currently selected measurement range 
OBSERVED AUTHORITY REQUIREMENTS
EMC 2014/30/EU
LVD 2014/35/EU
ATEX 2014/34/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011
EAC LVD TR-CU 004/2011
APPROVALS
ATEX KEMA 07ATEX0148 X
IECEx KEM 09.0052X
c FM us FM19US0059X / FM19CA0032X
c UL us, UL 61010-1 E314307
c UL us, UL 913 E233311 (only 9113xx-U9)
EAC Ex RU C-DK.HA65.B.00355/19
DNV-GL Marine TAA00000JD
ClassNK TA18527M
SIL SIL 2 certified & fully assessed acc. to IEC 61508