Veris H608 Current Switch

Features

  • Retrofit or new construction – high-performance devices in split-core housings
  • Adjustable trip point – precise current trip point setting
  • Low setpoint – minimum trip point as low as 0.5 A, no need for multiple wraps of the conductor through the sensor, even on loads as small as 1/5 hp
  • Small size – fits easily inside small enclosures
  • Self-gripping iris on split-core housings for easy installation
  • Status LEDs – for easy setup and local indication
  • Induced from monitored conductor sensor power
Enquiry
Category:

Veris Industries is an energy and environmental sensor partner that provides quality products for commercial HVAC and other automation applications. We offer complete lines of reliable, long-lasting innovative power monitoring products.

Hawkeye H608 adjustable current switches offer high performance, with a wide array of amperage range options. These products can accurately detect belt loss, coupling shear or other mechanical failure on unit vents, exhaust fans, recirculation pumps and other fixed loads down to as little as 1/5 hp.

Dimensional Drawing

Detects Belt Loss/Coupling Shear! Detects Belt Loss/Coupling Shear!

Now you can easily detect when drive belts slip, break, or pump couplings shear. In fact, a typical HVAC motor that loses its load has a reduction of current draw of up to 50%. That’s why our sensors are the industry standard for status.

Applications

  • Detecting belt loss, coupling shear, and mechanical failure
  • Verifying lighting circuit and other electrical service run times
  • Monitoring status of industrial process equipment
  • Monitoring status of critical motors (compressor, fuel, etc.)
  • VFD output on/off status

Specification

Model H608
Application Building Automation Systems
Current Measurement Range 0.5 – 175 A
Current Sensor type Current Switch, AC
Electrical Wiring Size 24 – 14 AWG (0.2 – 2.1 mm²)
Measurement Type AC Current
Monitored Frequency Range 50 – 60 Hz
Monitored Wire Size  0.5″ (12 mm)
Mounting Split Core
Operating Humidity 10 – 90% RH, non-condensing
Operating Temperature 5 – 140 °F (-15 – 60 °C)
Output Specifications N.O. 1 A @ 30 VAC/DC
Outputs Switch output
Product Certification UL | CE
Product Type Sensor
Range HX08 Series
Relay Coil Voltage None
Relay Contact Ratings None
Relay Poles/Throw None
Setpoint Adjustable
Warranty 5 years

Download

Veris-H608-Current Switch_DpstarGroup