Digital Controller – Shimaden MR13 Series

Features

  • 3-channel controller, 3-channel input, 3-channel setting and simultaneous 3-channel display are possible
  • Accuracy: ± (0.3% FS + 1 digit)
  • Follow-up type PV input function
  • Follow-up type SV setting function
  • Remote/local and DI input function
  • Programmable 1 pattern with 9-step function
  • Included a new processing system, Expert PID, remarkably improved PID control efficiency; overshoot and undershoot are controlled effectively.
  • Interface RS232C/RS485
Enquiry

MR13 Series is controller in 1 with input 3 points, setting 3 points, and output 3 points.

Specification

Display
LED display PV display 7-segment LED green 4 digits 3 channels to be displayed individually.
SV display 7-segment LED orange 4 digits
CH display 7-segment LED orange 1 digit
Action display LED Control output display: 3-OUT1, OUT2, OUT3
Auto tuning 1-AT
Follow type SV display 1-FLW Program RUN: 1-RUN
Event output display 3-EV1, EV2, EV3
Remote input display 1-REM Communication display: 1-COM
Display accuracy ±(0.3%FS + 1 digit) Standard accuracy
Temperature range in which accuracy is maintained 23 °C±5 °C
Display resolution Depends on measuring range (0.001, 0.01, 0.1, 1)
Sampling cycle 0.5 seconds
Measured value display range -10% to 110% of measuring range
Setting
Setting By 6 front key operation
Setting range Same as measuring range
Higher/lower limit setting limiter Higher and lower limits to be set separately; free within measuring range (Lower limit < higher limit)
Follow type SV setting SV of CH2 or CH3 can be set to follow CH1 (deviation setting) (on condition that measuring range of CH2 or CH3 is the same as that of CH1.)
Input
Input type has to be the same for 3 channels (measuring range can be selected individually).  
Thermocouple B, R, S, K, E, J, T, N, PL II, WRe5-26, {L, U (DIN43710)}
(Multiple input, multiple range. Refer to measuring range code table.)
External resistance 100Ω maximum
Input impedance 500kΩ minimum
Burnout Standard feature (up scale)
Cold junction temperature compensation accuracy ±2.0 °C (5–45 °C)
R.T.D. JIS Pt100/JPt100 3-wire type (Multiple range. Refer to measuring range code table.)
Amperage Approx. 0.25 mA
Lead wire tolerable resistance 5Ω maximum/wire
Voltage ±10, 0–10, 0–20, 0–50, 10–50, 0–100mV DC, or ±1,
0–1, 0–2, 0–5, 1–5, 0–10V DC
(Multiple input, programmable range. Refer to measuring range code table.)
Input impedance 500kΩ minimum
Current 4–20, 0–20mA DC
(Multiple input, programmable range. Refer to measuring range code table.)
Receiving impedance 250Ω
Sampling cycle 0.5 seconds
PV bias ±1999 digit
PV filter OFF, 1–100 seconds
Follow type PV input PV input of CH2 or CH3 can be set to follow CH1 (deviation setting) (on condition that measuring
range of CH2 or CH3 is the same as that of CH1.)
Isolation Insulated between input and various outputs (not insulated between input and system, remote input and DI input)
Control
Control mode Expert PID control with auto tuning function
Proportional band (P) OFF, 0.1–999.9%FS (OFF=ON/OFF action)
Integral time (I) OFF, 1–6000s (OFF=P, PD action with manual reset)
Derivative time (D) OFF, 1–3600s (OFF=P, PI action) Manual reset: ±50.0%
ON/OFF hysteresis 1–999 digit
Proportional cycle 0.5–120.0 seconds (0.5 sec. is unit for setting.)
Control output characteristics RA/DA selectable (set to RA when shipped)
Output limiter Higher limit, lower limit 0.0–100.0% (lower limit < Higher limit)
Soft start OFF, ON (Fixed to 10 sec.; Valid when power is turned on, RTS RUN, and when returned from scaleover.)
Control output/rating
Output specification has to be the same for 3 channels.  
Contact output (Y) 1a 240V AC 2.5A/resistive load
Current output ( I ) 4–20mA, 0–10mA DC/load resistance 600Ω maximum.
SSR drive voltage output (P) 15V±3V DC/ Load current 20mA maximum
Voltage output (V) 0–10V DC/Load current 2mA maximum
Operation output updating cycle 0.5 second
Isolation Insulated between control output and system and input (not insulated between control output I, P or V and analog output)
Event output (optional)
Number of outputs : 3 -EV1, EV2, EV3 (Selectable from CH1, CH2 and CH3, individual setting, individual output)
Output rating : Contact output 1a (common) 240V AC / 1A (resistive load)
Setting : Individual setting
0) NON : Not assigned
1) DEV : Higher limit deviation value alarm
2) DEV : Lower limit deviation value alarm
3) DEV : Higher/lower limit value alarm in case SV is out of measuring range
4) DEV : Higher/lower limit value alarm in case SV is within measuring range
5) PV : Higher limit absolute value alarm
6) PV : Lower limit absolute value alarm
7) SO : ON upon scaleover
8) RUN : ON during program RUN
9) END : ON for 1 sec. upon termination of program
10) STEP : ON for 1 sec. upon termination of program step
Hysteresis 1–999 digit (when DEV or PV has been selected)
Standby action Selectable (when DEV or PV has been selected)
Action delay time OFF, 1–9999 seconds (when DEV or PV has been selected)
Isolation Insulated between alarm output and various inputs/outputs and system
Remote setting (optional, selectable between this function and DI)  
Setting signal 1–5V, 0–10V, 4–20mA
Setting range Same as measuring range
Accuracy of setting ±(0.3%FS+1) digit
Channel for setting Selectable from CH1, CH2 and CH3
Remote scaling Within measuring range (inverted scaling possible)
Remote bias -1999–5000 digit
Remote filter OFF, 1–100 seconds
Sampling time 0.5 second
Isolation Insulated between remote input and various outputs (not insulated from system and various inputs)
External control input (DI) (optional, selectable between this function and remote setting)  
Number of input point 1
Input rating Non-voltage contact, open collector input (about 5V/0.4mA DC impress)
Action type NON, FLW (follow type SV), RST/ RUN, HLD and ADV
Isolation Insulated between DI input and various outputs (not insulated from system and various inputs)
Program (optional)
Registrable pattern 1
Number of steps 9 maximum
Program setting range
Level Same as measuring range
Time 1–9999 minutes/step
Ramp To be set automatically according to level and time
Number of executions 9999 maximum
PID output limiter To be set selectively from 3 types of PID & output limiter
External control input DI/non-voltage 1 point (RUN/RST, HLD, ADV)
Action status output RUN, END and STEP to be selectively output to event output
CH2 and CH3 in SV follow setting Program to be executed by making CH2 or CH3 deviation-follow to pattern set in CH1 in SV follow
setting. Not in SV follow setting, program is executed in FIX mode.
Additional functions Temporary suspension (HLD), carry-forward (ADV), PV start
Analog output (optional, selectable between this function and communication)  
Number of output 1
Output types Selectable from CH1_PV, CH2_PV, CH3_PV, CH1_SV, CH2_SV, CH3_SV, CH1_OUT, CH2_OUT and CH3_OUT
Output rating 0–10mV DC/Output impedance 10Ω
0–10V DC/Load current 1mA maximum
4–20mA DC/Load resistance 300Ω maximum
Output accuracy ±0.3%FS (to displayed value)
Output resolution Approx. 1/8000
Output updating cycle 0.5 seconds
Output scaling Within measuring range (inverted scaling possible
Isolation Insulated between analog output and various inputs and system (not insulated between analog output and control outputs I, P and V)
Communication (optional, selectable between this function and analog output)  
Communication type RS-232C, RS-485
Communication system Half duplex start-stop synchronous system
Communication speed 1200, 2400, 4800, 9600, 19200bps
Data format 7 bits, 8 bits, no parity, even parity selectable
Communication address 1–99
Communication code ASCII code
Communication protocol Shimaden standard protocol
Communication format Control code selectable, BCC check arithmetic system selectable
Isolation Insulated between communication signal and system/input/output
Others Meets the EMC standards with an additional clamp filter (E04SR301334, SEIWA Information Systems Co.,LTD)
Others
Data storage By non-volatile memory (EEPROM)
Ambient temperate/humidity ranges -10–50 °C/below 90% RH (on condition that there is no dew condensation)
Temperature for storage Between-20 and 65 °C
Power voltage 100V–260V AC ±10% (50/60 Hz)
Power consumption 18VA maximum
Input noise removal ratio Normal mode 45 dB minimum (50/60 Hz)
Common mode 140 dB minimum (50/60 Hz)
Applicable standard RoHS: EN50581
Insulation resistance power terminal Between input/output terminals
500V DC 20MΩ minimum
Between input/output terminals and protective conductor terminal: 500V DC 20MΩ minimum
Dielectric strength : 1 minute at 2300V AC between input/output terminals and power terminal (inductive current 5mA) 1 minute at 2300V AC between power terminal and ground terminal (inductive current 5mA)
Protective structure Dust and splash proof front panel equivalent to IP66 (applicable only when panel thickness is 1.2 to 3.2 mm)
Material PPE resin molding (equivalent to UL94V-1)
External dimensions 96 x 96 x 110 mm (Panel depth: 100 mm)
Mounting Push-in panel (one-touch mount)
Panel cutout size H92 x W92 mm
Weight Approx. 420 g

Ordering Information

ITEMS CODE SPECIFICATIONS
SERIES MR13 – MPU-Based 3 Channel Auto-Tuning PID Controller DIN 96 x 96mm
INPUT 1 Thermocouple B, R, S, K, E, J, T, N, PLII, WRe5-26, U, L Multi-input
Multi-range
2 R.T.D. Pt100 / JPt100 Multi-range
3 Voltage (mV) -10–10, 0–10, 0–20, 0–50, 10–50, 0–100mV DC Multi-input
Programmable
Range
4 Current (mA) 0–20, 4–20mA DC
6 Voltage (V) -1–1, 0–1, 0–2, 0–5, 1–5, 0–10V DC
CONTROL OUTPUT Y1- Contact: Proportional Cycle 0.5–120.0 sec.
Contact capacity: 240V AC 2.5A / resistive load
I1- Current: 4–20, 0–10mA DC Load resistance: 600Ω max.
P1- SSR drive voltage: Proportional Cycle 0.5–120.0 sec.
Output rating: 15V±3V DC / 20mA max.
V1- Voltage: 0–10V DC
Load current: 2mA max.
PROGRAM FUNCTION (OPTION) N None
P 1 Pattern, 9 step
EVENT OUTPUT (OPTION) 0 None
1 Contact (1a common): 240V AC 1A / resistive load EV1, EV2, EV3 / 3 Point
REMOTE OR DI INPUT (OPTION) 00 None
04 4–20mA DC Receiving resistance: 250Ω
05 1– 5V DC Input resistance: 500kΩ min.
06 0–10V DC Input resistance: 500kΩ min.
51 DI Non-Voltage Contact, Open Collector Input
ANALOG OUTPUT OR COMMUNICATION
FUNCTION (OPTION)
00 None
03 Voltage 0–10mV DC, Output resistance: 10Ω
04 Current 4–20mA DC, Load resistance: 300Ω max.
06 Voltage 0–10V DC, Load current: 1mA max.
15 RS-485
17 RS-232C
REMARKS 0 Without
9 With (Please consult before ordering.)

Download

Shimaden MR13 Series – Digital Controller-DpstarGroup