PR Electronics 9107B – HART Transparent Driver

Features

  • 24 VDC supply via power rail or connectors
  • Fast response time
  • High active output load 725 Ohm / 20 mA
  • Output line fault detection via status relay
  • SIL2 certified via Full Assessment according to IEC 61508

 

Enquiry
Category:

PR Electronics 9107B – HART Transparent Driver

Application

  • PR Electronics 9107B is a 1- or 2-channel isolated 1:1 driver barrier designed for intrinsic safety applications.
  • It controls I/P converters, valves, and indicators in hazardous areas.
  • It supports bi-directional transmission of HART communication signals.
  • PR Electronics 9107B can be installed in safe areas or in Zone 2 / Cl. 1, Div. 2 areas, transmitting signals to Zone 0, 1, 2, and Zone 20, 21, 22, including mining / Class I/II/III, Div. 1, Gr. A-G.

Features

  • The PR 45xx displays process values per channel and sets high and low limits for detecting loop current levels. The status relay activates if these limits are exceeded.
  • Dual channel versions can split signals (1 in, 2 out).

Advanced Features

  • The PR 45xx has a detachable display and green/red LEDs indicating operational status for each channel.
  • Each channel can be tagged.
  • Detects output line faults.
  • In the 1-channel version, the status relay can act as a simple limit switch.
  • Suitable for use in systems up to Performance Level “d” per ISO-13849.

Technical Characteristics

  • Provides high galvanic isolation of 2.6 kVAC.
  • High accuracy better than 0.1%.
  • Continuously checks vital stored data for safety.

Mounting

  • Can be mounted vertically or horizontally without spacing between adjacent units.

Specification

ENVIRONMENTAL CONDITIONS
Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20…28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II
MECHANICAL SPECIFICATIONS
Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501/451x 109 x 23.5 x 116 / 131 mm
Weight approx. 250 g
Weight incl. 4501 / 451x (approx.) 265 g / 280 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13…2.08 mm2 AWG 26…14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2…13.2 Hz ±1 mm
13.2…100 Hz ±0.7 g
COMMON SPECIFICATIONS
Supply
Supply voltage 19.2…31.2 VDC
Fuse 1.25 A SB / 250 VAC
Max. required power ≤ 1.0 W / ≤ 1.8 W (1 ch. / 2 ch.)
Max. power dissipation, 1 / 2 ch. ≤ 1.0 W / ≤ 1.8 W
Isolation voltage
Test /working: Input to any 2.6 kVAC / 300 VAC reinforced isolation
Analog output to supply 2.6 kVAC / 300 VAC reinforced isolation
Status relay to supply 1.5 kVAC / 150 VAC reinforced isolation
Response time
Response time (0…90%, 100…10%) < 5 ms
Programming PR 45xx
Signal dynamics, input Analog signal chain
Signal dynamics, output Analog signal chain
HART bi-directional communication frequency range 0.5…7.5 kHz
Signal / noise ratio > 60 dB
Accuracy Better than 0.1% of sel. range
mA, absolute accuracy ≤ ±16 μA
mA, temperature coefficient ≤ ±1.6 μA / °C
Effect of supply voltage change on output (nom. 24 VDC) < ±10 μA
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span
INPUT SPECIFICATIONS
Current input
Measurement range 3.5…23 mA
Sensor error detection: Loop break 4…20 mA < 1 mA
Input voltage drop, supplied unit < 2 V @ 23 mA
Input voltage drop, non-supplied unit < 4 V @ 23 mA
OUTPUT SPECIFICATIONS
Current output
Signal range 3.5…23 mA
Load (@ current output) ≤ 725 Ω
Load stability ≤ 0.01% of span / 100 Ω
Current limit ≤ 28 mA
Status relay
Relay function N.C.
Programmable low setpoint 0…29.9 mA
Programmable high setpoint 0…29.9 mA
Hysteresis for setpoints 0.1 mA
Max. voltage 125 VAC / 110 VDC
Max. current 0.5 AAC / 0.3 ADC
Max. voltage – hazardous installation 32 VDC / 32 VAC
Max. current – hazardous installation 1 ADC / 0.5 AAC
of span = normal measurement range 4…20 mA
OBSERVED AUTHORITY REQUIREMENTS
EMC 2014/30/EU
LVD 2014/35/EU
ATEX 2014/34/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011
APPROVALS
ATEX DEKRA 11ATEX0247 X
IECEx DEK 11.0088X
c FM us FM16US0465X / FM16CA0213X
INMETRO DEKRA 16.0002 X
c UL us, UL 61010-1 E314307
c UL us, UL 913 E233311 (only 9107xx-U9)
EAC Ex RU C-DK.HA65.B.00355/19
DNV-GL Marine TAA00000JD
ClassNK TA18527M
SIL SIL 2 certified & fully assessed acc. to IEC 61508

Download

PR Electronic 9107B HART transparent driver-DpstarGroup