PR Electronics 5106B – HART Transparent Repeater

Features

  • 3- / 5-port 3.75 kVAC galvanic isolation
  • Low response time
  • 2-wire supply > 17 V in Ex / I.S. area
  • 1- or 2-channel version
  • Universal supply by AC or DC
Enquiry
Category:

PR Electronics 5106B – HART Transparent Repeater

Application

  • PR Electronics PR5106B is designed for use as a power supply and Ex/IS safety barrier with two-way HART communication for 2-wire transmitters in hazardous areas.
  • It also serves as an Ex/IS safety barrier with two-way HART communication for current-supplied transmitters installed in hazardous areas.
  • Additionally, it functions as a signal isolator with rapid response times for analog current signals from hazardous areas.

Technical Specifications

  • PR Electronics PR5106B primarily handles current signals ranging from 4 to 20 mA.
  • It utilizes microprocessor technology for precise adjustment of gain and offset. The analog signal is transmitted with a response time of under 25 ms.
  • Inputs, outputs, and power supply are isolated and galvanically separated.
  • The output can be configured for use as either an active current transmitter or a 2-wire transmitter.

Mounting/Installation

  • It can be mounted vertically or horizontally on a DIN rail. Units can be placed without spacing between neighboring units, allowing for up to 84 channels per meter.
  • PR Electronics PR5106B is recommended as an Ex/IS safety barrier for models 5335D and 6335D.

Specification

ENVIRONMENTAL CONDITIONS
Operating temperature -20°C to +60°C
Calibration temperature 20…28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
MECHANICAL SPECIFICATIONS
Dimensions (HxWxD) 109 x 23.5 x 130 mm
Weight approx. 245 g
DIN rail type DIN 46277
Wire size 1 x 2.5 mm2 stranded wire
Screw terminal torque 0.5 Nm
COMMON SPECIFICATIONS
Supply
Supply voltage, universal 21.6…253 VAC, 50…60 Hz or 19.2…300 VDC
Fuse 400 mA SB / 250 VAC
Max. required power ≤ 3 W (2 channels)
Internal power dissipation ≤ 2 W (2 channels)
Isolation voltage
Isolation voltage, test / working 3.75 kVAC / 250 VAC
PELV/SELV IEC 61140
Response time
Response time (0…90%, 100…10%) < 25 ms
Auxiliary supplies
2-wire supply (pin 44…42 and 54…52) 25…17 VDC / 0…20 mA
Signal / noise ratio Min. 60 dB (0…100 kHz)
Accuracy Better than 0.1% of sel. range
Effect of supply voltage change < ±10 μA
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span
INPUT SPECIFICATIONS
Current input
Measurement range 4…20 mA
Min. measurement range (span) 16 mA
Input resistance: Supplied unit Nom. 10 Ω
Input resistance: Non-supplied unit Rshunt = ∞, Vdrop < 4 V
OUTPUT SPECIFICATIONS
Current output
Signal range 4…20 mA
Min. signal range 16 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Current limit ≤ 28 mA
Passive 2-wire mA output
Signal range 4…20 mA
Max. external 2-wire supply 29 VDC
Effect of external 2-wire supply voltage variation < 0.005% of span / V
Output ripple < 3 mVRMS on HART communication
of span = of the presently selected range
OBSERVED AUTHORITY REQUIREMENTS
EMC 2014/30/EU
LVD 2014/35/EU
EAC TR-CU 020/2011
APPROVALS
ATEX DEMKO 00ATEX127483, II (1) G [EEx ia] IIC
UL UL 913, UL 508
EAC Ex RU C-DK.HA65.B.00355/19

Download

PR Electronic 5106B HART transparent repeater-DpstarGroup