Loop Powered Isolator – PR Electronics 3185

Features

  • 1 or 2 channel input loop powered isolator
  • Signal 1:1 functional range 0…23 mA
  • Low input voltage drop and fast response time
  • Excellent accuracy and high load stability
  • Slimline 6 mm housing
Enquiry
Category:

Application

  • 1:1 input loop powered isolator of current signals in the range 0(4)…20 mA.
  • 3185 is an easy mounting DIN rail unit.
  • A very competitive choice in terms of both price and technology for galvanic isolation of current signals.
  • Provides surge suppression and protects control systems from transients and noise.
  • 3185 eliminates ground loops and can be used for measuring floating signals.
  • The device can be mounted in Safe area or in Zone 2 and Cl. 1 Div 2. area.

Technical characteristics

  • 3185 is powered by the analog input current signal loop.
  • Low input voltage drop, typ 1.35 V + Vout.
  • Excellent conversion accuracy, better than 0.1% in the range 0…20.5 mA.
  • Functional range is 0…23 mA which means that 3185 is NAMUR NE43 compliant.
  • Inputs and outputs are floating and galvanically separated.
  • The output is voltage limited to 17.5 VDC.
  • High galvanic isolation of 2.5 kVAC.
  • Fast response time < 5 ms.
  • Excellent signal/noise ratio > 60 dB.

Mounting / installation / programming

  • DIN rail mounting with up to 330 channels per meter.
  • Temperature operation range is from -25…+70°C.

Specification

ENVIRONMENTAL CONDITIONS
Operating temperature -25°C to +70°C
Storage temperature -40°C to +85°C
Calibration temperature 20…28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II
MECHANICAL SPECIFICATIONS
Dimensions (HxWxD) 113 x 6.1 x 115 mm
Weight approx. 70 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13…2.5 mm2 / AWG 26…12 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2…25 Hz ±1.6 mm
25…100 Hz ±4 g
COMMON SPECIFICATIONS
Supply
Power dissipation, per channel 30 mW
Isolation voltage
Isolation voltage, test / working 2.5 kVAC / 300 VAC (reinforced)
Zone 2 / Div. 2 250 VAC
Response time
Response time (0…90%, 100…10%) < 5 ms
Signal / noise ratio > 60 dB
Signal dynamics, input Analog signal chain
Signal dynamics, output Analog signal chain
Accuracy Better than 0.1%
Cut-off frequency (3 dB) 100 Hz
EMC immunity influence < ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of span
INPUT SPECIFICATIONS
Current input
Measurement range 0…23 mA
Input voltage drop (Unit voltage drop) + Vout.
Signal conversion 1:01
Start-up current, typ. 10 uA
Current input overload, max. 50 mA
Input to output voltage drop, typ. 1.35 V + (0.015 x Vout.)
OUTPUT SPECIFICATIONS
Current output
Signal range 0…23 mA
Load (@ current output) ≤ 600 Ω
Load stability < 0.01% of span / 100 Ω
Voltage limit 17.5 V
of span = 0…20 mA
I.S. / EX MARKING
ATEX II 3 G Ex nA IIC T4 Gc
IECEx Ex nA IIC T4 Gc
FM, US Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, AEx nA IIC T4
FM, CA Cl. I, Div. 2, Gp. A, B, C, D T4 or Cl. I, Zone 2, Ex nA IIC T4
EAC Ex 2Ex nA IIC T4 Gc X
OBSERVED AUTHORITY REQUIREMENTS
EMC 2014/30/EU
LVD 2014/35/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011
APPROVALS
ATEX KEMA 10ATEX0147 X
IECEx KEM 10.0068X
c FM us FM17US0004X / FM17CA0003X
UL UL 61010-1
DNV-GL Marine TAA00001RW
EAC Ex RU C-DK.HA65.B.00355/19

Download

PR Electronic 3185 Loop powered isolator-DpstarGroup