Shimaden SRP30 Series – Hybrid Controller

Features

  • Adopts a large LCD for SRP33 (display area: 77 (W) × 57 mm (H))
  • Improved visibility and expressibility with a large 5-digit and 11-segment display
  • Achieves high precision of 0.1%FS and high resolution of 0.0001
  • The fastest sampling cycle is 50 ms (selectable from 50, 100, 200, and 500 ms).
  • Multi SV value setting: SV value can be set up to 9 points.
  • Multi PID: PID No. 1–9 (9 types)
  • Program function: up to 9 patterns and 180 steps
  • Dust and splash proof front panel equivalent to IP55
Enquiry

Shimaden SRP30 Series functions as both a top-tier controller and a high-performance program controller. Its exclusive setup software allows for initial configuration on a PC, and the set data can be effortlessly transferred to the device via the front panel USB port, even without the controller being powered.

Ordering Information

ITEM CODE SPECIFICATIONS
.

.SERIES

SRP33- 96 x 96 DIN size Hybrid controller……………………………… TC, RTD, mV, V, mA Full multi input (mA is input by externally attached resistor) DI2 points, EV3 points, USB Communication SRP34- 48 x 96 DIN size standard equipment
SRP34- 48 x 96 DIN size Hybrid controller
v

d

CONTROL OUTPUT 1

Y Contact: 1a contact capacity 240 V AC 2.5 A/resistive load, 1 A/inductive load
I Current: 4–20 mA DC, Load resistance: 600Ω or below
P SSR drive voltage: 12 V ± 1.5 V DC, Load current: 20 mA or below
V Voltage: 0–10 V DC, Load current: 2 mA or below
.

.

.

CONTROL OUTPUT 2
(OPTION)

N- Without
Y- Contact: 1a contact capacity 240 V AC 2.5 A/resistive load, 1 A/inductive load
I- Current: 4–20 mA DC, Load resistance: 600Ω or below
P- SSR drive voltage: 12 V ± 1.5 V DC, Load current: 20 mA or below
V- Voltage: 0–10 V DC, Load current: 2 mA or below
E- EV4 Contact, 1a contact capacity, 240 V AC 2.5 A/resistive load, 1 A/inductive load
.

EXTERNAL CONTROL INPUT (DI) (OPTION)

0 Without
1 5 points (DI3–7) *3
.

.

ANALOG OUTPUT (AO)
(OPTION)

0 Without
3 Voltage: 0–10 mV DC, Output resistance: 10Ω
4 Current: 4–20 mA DC, Load resistance: 300Ω or below
6 Voltage: 0–10 V DC, Load current: 2 mA or below
.

EXTERNAL CONTROL OUTPUT (DO) (OPTION)

0 Without
1 3 points (DO1–3)
Darlington open collector output: 24 V DC 50 Ma
.

.

.

ADDITIONAL DO/CT/REM (OPTION)

0 Without
1 Additional DO3 points (DO4–6)
Darlington open collector output: 24 V DC 50 mA *1
2 CT input 2 points, amperage display 0.0–55.0 A *2
4 Remote setting input 4–20 mA DC/receiving impedance 250Ω (Uninsulated)
5 Remote setting input 1–5 V DC/input resistance approximately 500kΩ (Uninsulated)
6 Remote setting input 0–10 V DC/input resistance approximately 500kΩ (Uninsulated)
.

.COMMUNICATION (OPTION)

0 Without
5 RS-485 Shimaden standard protocol/MODBUS communication protocol
7 RS-232C
.

REMARKS

0 Without
9 With

 

Download