PR Electronics 5350B – Profibus PA / Foundation Fieldbus Transmitter

Features

  • PROFIBUS PA ver. 3.0
  • FOUNDATION Fieldbus ver. ITK 4.6
  • Automatic switch between protocols
  • FISCO-certified
  • Basic or LAS capability with F.F.
Enquiry

PR Electronics 5350B – Profibus PA / Foundation Fieldbus Transmitter

Application

  • Measurement of temperature using RTD or TC sensors in a linearized manner.
  • Temperature measurement involving difference, average, or redundancy using RTD or TC sensors.
  • Measurement of linear resistance, potentiometer, and bipolar mV.

Technical Specifications

  • Bus transmitter supporting PROFIBUS PA and FOUNDATION Fieldbus communications. It seamlessly switches between the two protocols.
  • Configuration for PROFIBUS PA is compatible with Siemens Simatic® PDM®, ABB Melody / Harmony, and Metso DNA software. For FOUNDATION Fieldbus, configuration can be done using Emerson DeltaV, Yokogawa CS 1000 / CS 3000, ABB Melody / Harmony, and Honeywell Experion software.
  • Simulation mode activation via magnet.
  • Polarity-independent bus connection.
  • High-resolution 24-bit A/D converter.
  • PROFIBUS PA function blocks: 2 analog.
  • FOUNDATION Fieldbus function blocks: 2 analog and 1 PID.
  • FOUNDATION Fieldbus capability: Basic or LAS.

Mounting / Installation

  • Suitable for DIN form B sensor head mounting.

Specification

ENVIRONMENTAL CONDITIONS
Operating temperature -40°C to +85°C
Calibration temperature 20…28°C
Relative humidity < 95% RH (non-cond.)
Protection degree (encl./terminal) IP68 / IP00
MECHANICAL SPECIFICATIONS
Dimensions Ø 44 x 20.2 mm
Weight approx. 55 g
Screw terminal torque 0.4 Nm
Vibration DIN class B, IEC 60068-2-6 and IEC 60068-2-64
2…25 Hz ±1.6 mm
25…100 Hz ±4 g
COMMON SPECIFICATIONS
Supply
Supply voltage 9.0…30 VDC
Supply voltage in FISCO installations 9.0…17.5 VDC
Max. required power < 350 mW
Isolation voltage
Test voltage 1.5 kVAC for 60 s
Working voltage 50 VRMS / 75 VDC
Response time
Response time (programmable) 1…60 s
Quiescent current < 11 mA
Max. current increase in the event of an error < 7 mA
Warm-up time 30 s
Signal / noise ratio Min. 60 dB
Updating time < 400 ms
Execution time, analog input < 50 ms
Accuracy Better than 0.05% of selected range
Signal dynamics, input 24 bit
EMC immunity influence < ±0.1% of reading
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1% of reading
INPUT SPECIFICATIONS
RTD input
RTD type Pt25…1000, Ni25…1000, Cu10…1000, lin. R, potentiometer
Cable resistance per wire 50 Ω (max.)
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Yes
Short circuit detection < 15 Ω
TC input
Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5
Cold junction compensation (CJC) < ±0.5°C
Sensor error detection Yes
Sensor error current: When detecting / else Nom. 4 μA / 0 μA
Short circuit detection < 3 mV
Voltage input
Measurement range -800…+800 mV
Input resistance 10 MΩ
OUTPUT SPECIFICATIONS
PROFIBUS PA connection
PROFIBUS PA protocol Profile A&B, ver. 3.0
PROFIBUS PA protocol standard EN 50170 vol. 2
PROFIBUS PA address (at delivery) 126
PROFIBUS PA function blocks 2 analog
FOUNDATION Fieldbus connection
FOUNDATION Fieldbus protocol FF protocol
FOUNDATION Fieldbus protocol standard FF design specifications
FOUNDATION Fieldbus version ITK 4.6
FOUNDATION Fieldbus capability Basic or LAS
FOUNDATION Fieldbus function blocks 2 analog and 1 PID
OBSERVED AUTHORITY REQUIREMENTS
EMC 2014/30/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
APPROVALS
ATEX KEMA 02ATEX1318 X
IECEx BVS 12.0035X
FM 3015609
CSA 1418937
INMETRO DEKRA 18.0006 X
NEPSI GYJ14.1101X
EAC Ex RU C-DK.HA65.B.00355/19

Download