PR Electronics 9116A – Universal Converter

Features

  • Input for RTD, TC, Ohm, potentiometer, mA and V
  • Supply for 2-wire transmitters
  • Active / passive mA output and relay output
  • Can be supplied separately or installed on power rail, PR type 9400
  • SIL 2-certified via Full Assessment
Enquiry
Category:

PR Electronics 9116A – Universal Converter

Advanced features

  • Configuration and monitoring using a detachable display front (PR 45xx); includes process calibration, signal and relay simulation.
  • Advanced relay configuration options, such as setpoint, window, delay, sensor error indication, and power monitoring.
  • Capability to copy configurations from one device to others of the same type via the display front.
  • Thermocouple (TC) inputs with internal or external Cold Junction Compensation (CJC) for higher accuracy.
  • Active or passive mA output available via the same two terminals.

Applications:

  • Can be mounted in safe areas or in Zone 2 / Class I, Division 2, Groups A, B, C, D.
  • Suitable for converting and scaling temperature, voltage, potentiometer, and linear resistance signals.
  • Functions as a power supply and signal isolator for 2-wire transmitters.
  • Monitors error events and cable breakage via individual status relays and/or a collective electronic signal through the power rail.
  • Designed, developed, and certified for use in SIL 2 applications according to IEC 61508 requirements.
  • Suitable for use in systems up to Performance Level “d” as per ISO-13849.

Technical Characteristics:

  • One green and one red front LED indicate operational status and malfunction. A yellow LED indicates relay status.
  • Provides 2.6 kVAC galvanic isolation between input, output, and supply.

Mounting:

  • Can be mounted vertically or horizontally without any distance between adjacent units.

Specification

ENVIRONMENTAL CONDITIONS
Operating temperature -20°C to +60°C
Storage temperature -20°C to +85°C
Calibration temperature 20…28°C
Relative humidity < 95% RH (non-cond.)
Protection degree IP20
Installation in Pollution degree 2 & meas. / overvoltage cat. II
MECHANICAL SPECIFICATIONS
Dimensions (HxWxD) 109 x 23.5 x 104 mm
Dimensions (HxWxD) w/ 4501/451x 109 x 23.5 x 116 / 131 mm
Weight approx. 185 g
Weight incl. 4501 / 451x (approx.) 200 g / 215 g
DIN rail type DIN EN 60715/35 mm
Wire size 0.13…2.08 mm2 AWG 26…14 stranded wire
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2…13.2 Hz ±1 mm
13.2…100 Hz ±0.7 g
COMMON SPECIFICATIONS
Supply
Supply voltage 19.2…31.2 VDC
Fuse 1.25 A SB / 250 VAC
Max. required power ≤ 2.1 W
Max. power dissipation ≤ 1.7 W
Isolation voltage
Test /working: Input to any 2.6 kVAC / 300 VAC reinforced isolation
Analog output to supply 2.6 kVAC / 300 VAC reinforced isolation
Status relay to supply 1.5 kVAC / 150 VAC reinforced isolation
Response time
Temperature input, programmable (0…90%, 100…10%) 1…60 s
mA / V input (programmable) 0.4…60 s
Auxiliary supplies
9116x1x: 2-w. sup. (term. 54…52) 28…16.5 VDC / 0…20 mA
9116x2x: 2-w. sup. (term. 54…52) 21.4…16.5 VDC / 0…20 mA
Programming PR 45xx
Signal dynamics, input 24 bit
Signal dynamics, output 16 bit
Signal / noise ratio Min. 60 dB (0…100 kHz)
Accuracy Better than 0.1% of sel. range
INPUT SPECIFICATIONS
RTD input
RTD type Pt10/20/50/100/200/250/300/Pt400/500/1000; Ni50/100/120/1000
Cable resistance per wire 50 Ω (max.)
Sensor current Nom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor error detection Programmable ON / OFF
Short circuit detection Yes
TC input
Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC) via ext. sensor in 5910 20…28°C ≤ ±1°C, -20…20°C / 28…70°C ≤ 2°C
CJC via int. mounted sensor ±(2.0°C + 0.4°C * Δt)
Δt = Internal temp.-ambient temp.
Sensor error detection Programmable ON or OFF (only wire breakage)
Current input
Measurement range 0…23 mA
Programmable measurement ranges 0…20 and 4…20 mA
Input resistance Nom. 20 Ω + PTC 50 Ω
Sensor error detection Loop break 4…20 mA
Voltage input
Measurement range 0…12 VDC
Programmable measurement ranges 0/0.2…1, 0/1…5, 0/2…10 VDC
Input resistance Nom. >10 MΩ
OUTPUT SPECIFICATIONS
Current output
Signal range 0…23 mA
Programmable signal ranges 0…20/4…20/20…0/20…4 mA
Load (@ current output) ≤ 600 Ω
Load stability ≤ 0.01% of span / 100 Ω
Sensor error indication 0 / 3.5 / 23 mA / none
NAMUR NE43 Upscale/Downscale 23 mA / 3.5 mA
Current limit ≤ 28 mA
Passive 2-wire mA output
Max. external 2-wire supply 26 VDC
Max. load resistance [Ω] (Vsupply-3.5)/0.023 A
Effect of external 2-wire supply voltage variation < 0.005% of span / V
Relay output
Relay functions Setpoint, Window, Sensor error, Power and Off
Max. voltage 250 VAC / VDC
Max. current 2A
Max. AC power 500 VA
Max. DC current, resistive load ≤ 30 VDC 2 ADC
Max. DC current, resistive load > 30 VDC See manual for details
Status relay
Max. voltage 125 VAC / 110 VDC
Max. current 0.5 AAC / 0.3 ADC
Max. AC power 62.5 VA / 32 W
OBSERVED AUTHORITY REQUIREMENTS
EMC 2014/30/EU
LVD 2014/35/EU
ATEX 2014/34/EU
RoHS 2011/65/EU
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011
EAC LVD TR-CU 004/2011
APPROVALS
ATEX KEMA 10ATEX0053 X
IECEx KEM 10.0022X
c FM us FM19US0058X / FM19CA0031X
c UL us, UL 61010-1 E314307
c UL us, UL 913 E233311 (only 9116xx-U9)
EAC Ex RU C-DK.HA65.B.00355/19
DNV-GL Marine TAA00000JD
ClassNK TA18527M
SIL SIL 2 certified & fully assessed acc. to IEC 61508

Download

PR Electronic 9116A Universal converter-DpstarGroup